Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Compact 1-phase Type 2 (or 3) surge protector - 120 V -Pluggable

DS215-120
Part Number 451601
DS215-120
  • Discover our latest innovation : the DAC15C-20-150
  • Compact single-phase type 2 (or 3) surge protector
  • In : 5 kA
  • Imax : 15 kA
  • Common mode
  • Pluggable module
  • Remote signaling option
  • EN 61643-11, IEC 61643-11 compliance
  • UL1449 ed.5

The DS215 Type 2 surge protectors are compact devices designed to protect single phase networks at the main switchboard. They provide a common or common/differential mode protection. This SPD is based on high energy varistor equipped with thermal disconnectors and failure indicator to comply with standards. The DS215 is DIN rail compatible and is built with a plug-in module and fixed base, which allows an easy and fast maintenance.

Select another reference:

SPD type
2 (or 3)
Network
120 V single-phase
AC system
TN
Nominal line voltage
Un 120 Vac
Max. AC operating voltage
Uc 150 Vac
Max. load current
if series connection
IL 20 A
Temporary Over Voltage (TOV) Characteristics - 5 sec.
Without disconnection
UT 180 Vac withstand
Temporary Over Voltage (TOV) Characteristics - 120 mn
Without disconnection or with safety disconnection
UT 230 Vac disconnection
Residual Current
Leakage current to Ground
Ipe < 0.5 mA
Follow current
If None
Nominal discharge current
15 x 8/20 µs impulses
In 5 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 15 kA
Withstand on Combination waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
Uoc 10 kV
Connection mode(s)
L/PE and N/PE
Protection mode(s)
Common mode
Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA 0.6 kV
Protection level CM/DM
@ In (8/20µs)
Up mc/md 0.6 kV
Admissible short-circuit current
Isccr 10 000 A
Technology
MOV
SPD configuration
Single phase
Connection to Network
By screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE)
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Housing material
Thermoplastic UL94 V-0
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Failsafe mode
Disconnection from AC network
Disconnection indicator
2 mechanical indicators
Spare module(s)
DSM215-120
Remote signaling of disconnection
Option DS215S-120 : output on changeover contact
Dimensions
See diagram
Standards compliance
IEC 61643-11 / EN 61643-11 / UL1449 ed.5
Certification
UL / CSA
Thermal disconnector
Internal
Installation ground fault breaker
Type 'S' or delayed
Back-up protection device
20 A min. - 125 A max. - Fuses type gG