Type 1 AC surge protector
Select another reference:
SPD type following IEC test |
1+2 |
Max. AC operating voltage L-N |
530 Vac |
Max. load current |
100 A |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
630 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
930 Vac disconnection |
Residual Current Leakage current to Ground |
< 2 mA |
Follow current |
None |
Nominal discharge current 15 x 8/20 µs impulses |
60 kA |
Max. discharge current max. withstand @ 8/20 µs by pole |
140 kA |
Impulse current by pole max. withstand 10/350µs by pole |
15 kA |
Total lightning current max. total withstand @ 10/350µs |
45 kA |
Admissible short-circuit current |
100000 A |
Protection level @ In (8/20µs) |
3 kV |
Specific energy by pole max. withstand 10/350 µs |
72 kJ/ohm |
Mounting |
Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Disconnection indicator | 3 mechanical indicators |
Remote signaling of disconnection |
Output on changeover contact |
Dimensions |
See diagram |
Certification |
EAC |
Standards compliance |
IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Thermal disconnector | Internal |
Installation ground fault breaker | Type 'S' or delayed |
Fuses |
Fuses Type gG - 125 A |