Type 1+2 AC surge protector - 1-pole
DAC1-13-10-440
Part Number: 821710411
- Type 1 + 2 AC surge protector
- In : 20 kA
- Iimp : 12,5 kA
- Pluggable module for each phase
- Remote signaling (option)
- EN 61643-11, IEC 61643-11 compliance

The DAC1-13 is an extreme duty Type 1+2 pluggable SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod.
The technology ‘Multi-varistor” allows a very high discharge current capability in small dimensions and the best possible behavior to the AC network (no follow current).
Despite their high discharge capability, the DAC1-13 surge protectors are especially compact and are available in multipolar versions to protect single or 3-phase AC networks.
Select another reference:
- DAC1-13-10-150
- DAC1-13-10-275
- DAC1-13-10-320
- DAC1-13-10-440
- DAC1-13-11-150
- DAC1-13-11-275
- DAC1-13-11-320
- DAC1-13-20-150
- DAC1-13-20-275
- DAC1-13-20-320
- DAC1-13-20-440
- DAC1-13-30-150
- DAC1-13-30-275
- DAC1-13-30-320
- DAC1-13-30-440
- DAC1-13-31-150
- DAC1-13-31-275
- DAC1-13-31-320
- DAC1-13-40-150
- DAC1-13-40-275
- DAC1-13-40-320
- DAC1-13-40-440
SPD type following IEC test |
1+2 |
Max. AC operating voltage L-N |
440 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
580 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
770 Vac disconnection |
Residual Current Leakage current to Ground |
< 1 mA |
Follow current |
None |
Nominal discharge current 15 x 8/20 µs impulses |
20 kA |
Max. discharge current max. withstand @ 8/20 µs by pole |
50 kA |
Impulse current by pole max. withstand 10/350µs by pole |
12.5 kA |
Withstand on overvoltages IEEE C62.41.1 |
20 kV |
Admissible short-circuit current |
50000 A |
Protection level @ In (8/20µs) |
1.7 kV |
Specific energy by pole max. withstand 10/350 µs |
40 kJ/ohm |
Technology | MOV |
SPD configuration | 1-pole |
Connection to Network | by screw terminals: 2.5-25 mm² |
Format |
Plug-in modular box |
Mounting |
Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Failsafe behavior | Disconnection |
Disconnection indicator | 1 mechanical indicator |
Spare module(s) |
MDAC1-13-440 |
Remote signaling of disconnection |
option DAC1-13S-10-440: output on changeover contact |
Dimensions |
See diagram |
Weight |
0.176 kg |
Certification |
- |
Standards compliance |
IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Installation ground fault breaker | Type 'S' or delayed |
Thermal disconnector | Internal |
Fuses |
Fuses Type gG - 125 A |