Contact : +33 1 41 23 50 23 (9:00 – 17:00 CEST)

Surge circuit breaker for protection of Type 2 AC SPD

SSD80S-40-230
Part Number 802114
SSD80S-40-230
  • SPD Specific Disconnectors (SSD) for short circuit protection of Type 2 AC surge protectors

  • Surge current withstand: 80 kA @ 8/20µs

  • Wide range of short circuit current protected

  • Reusable after switch triggered

  • Low rated tripping current with time-current characteristics for overcurrent coordination with upstream OCPD and safety disconnect in case of SPD failure


The SSD range has been especially designed to be associated with SPDs. These very specific devices with built-in GDT are able to conduct huge surge currents in rather small dimensions to protect Type 2 SPDs against harsh current circuit failures, furthermore, the coil in the SSD can cut off the minimum fault current. In order to comply IEC 61643-11 standards, AC power SPD must be protected against short circuit failures: these specific SPD disconnectors must be installed in the SPD branch.


Minimum delay tripping current
Id 3A@<5s
Rated impulse withstand voltage
Uimp 4 kV
Minimum instantaneous tripping current
Ii 5A@<0.1s
Nominal line voltage
Un 230/400 Vac
Nominal discharge current
15 x 8/20 µs impulses
In 40 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax 80 kA
Equivalent rated AC current
125 A
Breaking capacity
100 000 A
Residual voltage
Up < 2.8 kV(+SPD)
Rated insulation voltage
Ui
Ui 400 Vac
Format
Monobloc modular box
Mounting
Symmetrical rail 35 mm (EN 60715)
Operating temperature
Tu -40/+85°C
Protection rating
IP20
Remote signaling of disconnection
Output on changeover contact
Wiring for remote signaling
0.75 mm² max.
Max. Voltage/Current for remote signaling
240 V / 2 A (AC) , 24 V / 6 A (DC)
Remote signaling of disconnection via control module
With attached seperated module
Dimensions
See diagram - 1TE (EN43880)
Standards compliance
GB/T 18802.11 / IEC 61643-11 / NB/T 42150
Certification
CQC