Type 1+2 AC surge protector - 1-pole
DS250VG-300
DS250VG-300
Part Number: 2577
  • Type 1+2+3 unipolar surge protector
  • 25 kA on 10/350µs impulse
  • Low voltage Up
  • Internal disconnection, status indicator and remote signaling
  • Optimized to TOV
  • IEC 61643-11 compliance
  • UL1449 ed.4 recognition
Installation Sheet

The DS250VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DS250VG is one-pole SPD and can be used in common mode or common and differential mode.

DS250VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.



SPD type
following IEC test
1+2+3
Network
230/400 V
Nominal line voltage
230 Vac
Max. AC operating voltage L-N 255 Vac
Max. load current
100 A
Temporary Over Voltage (TOV) Charasteristics - 5 sec.
without disconnection
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120 mn
without disconnection or with safety disconnection
440 Vac withstand
Residual Current
Leakage current to Ground
None
Follow current
None
Nominal discharge current
15 x 8/20 µs impulses
30 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
70 kA
Impulse current by pole
max. withstand 10/350µs by pole
25 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50µs - 8/20µs
20 kV
Withstand on overvoltages IEEE C62.41.1 20 kV
Admissible short-circuit current 50000 A
Connection mode(s)
L/N or L/PE
Protection mode(s)
Common Mode or Differential Mode
Protection level
@ In (8/20µs)
1.5 kV
Residual voltage
@ In (8/20 µs) Ures
1.1 kV
Protection level L/PE
@ In (8/20µs)
1.5 kV
Specific energy by pole
max. withstand 10/350 µs
156 kJ/ohm
 
Technology VG
SPD configuration 1-pole
Connection to Network By screw terminals : 6-35 mm² / by bus
Format 1-pole modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85°C
Protection rating IP20
Outdoor application
False
Failsafe behavior Disconnection
Disconnection indicator 1 mechanical indicator
Remote signaling of disconnection Output on changeover contact
Dimensions
See diagram
Certification UL / CSA / EAC
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses
Fuses type gG - 315 A