Type 1+2 AC surge protector - 3-phase
DS133VG-230
Part Number: 571563
- Type 1 + 2 + 3 AC surge protector
- In : 20 kA
- Iimp total : 37.5 kA on 10/350µs impulse
- Pluggable module
- Optimized to TOV
- Remote signaling (option)
- EN 61643-11, IEC 61643-11 and UL1449 ed.4 compliance

The DS130VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DS130VG is one-pole SPD and can be used in common mode or common and differential mode.
DS130VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
Select another reference:
SPD type following IEC test |
1+2+3 |
Network |
230/400 V 3-phase |
AC system |
TNC |
Nominal line voltage |
230 Vac |
Max. AC operating voltage L-N |
255 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
180 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
230 Vac withstand |
Residual Current Leakage current to Ground |
None |
Follow current |
None |
Nominal discharge current 15 x 8/20 µs impulses |
20 kA |
Max. discharge current max. withstand @ 8/20 µs by pole |
50 kA |
Impulse current by pole max. withstand 10/350µs by pole |
12.5 kA |
Total lightning current max. total withstand @ 10/350µs |
37.5 kA |
Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs - 8/20µs |
6 kV |
Withstand on overvoltages IEEE C62.41.1 |
20 kV |
Admissible short-circuit current |
25000 A |
Connection mode(s) |
L/PE |
Protection mode(s) |
Common mode |
Residual voltage @ In (8/20 µs) |
0.6 kV |
Protection level L/PE @ In (8/20µs) |
1.25 kV |
Specific energy by pole max. withstand 10/350 µs |
40 kJ/ohm |
Technology | VG |
SPD configuration | 3-phase |
Connection to Network | By screw terminals: 2.5-25 mm² / by bus |
Format |
Plug-in modular box |
Mounting |
Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Failsafe behavior | Disconnection |
Disconnection indicator | 1 mechanical indicator by pole |
Spare module(s) |
DSM130VG-230 |
Remote signaling of disconnection |
option DS133VGS-230 : output on changeover contact |
Dimensions |
See diagram |
Certification |
EAC |
Standards compliance |
IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Installation ground fault breaker | Type 'S' or delayed |
Thermal disconnector | Internal |
Fuses |
Fuses Type gG - 125 A |