Type 1+2 AC surge protector - 1-pole
DAC1-13VG-10-275
Part Number: 821730211
- Type 1 + 2 + 3 AC surge protector
- VG Technology
- In : 20 kA
- Iimp : 12,5 kA on 10/350µs impulse
- No leakage current
- Pluggable module for each phase
- Remote signaling (option)
- Optimized to TOV
- EN 61643-11, IEC 61643-11 and UL1449 ed.4 compliance

The DAC1-13VG is an extreme duty pluggable Type 1+2+3 SPD designed to protect AC powerline at the main switchboard of an installation equipped with lightning rod.
Equipped with exclusive CITEL’s VG technology, the range achieves an high protection level, guaranteeing a maximum protection efficiency, a absence of follow and leakage currents, a simplification of use (no additional lightning arrester required) and a maximum lifetime.
The DAC1-13VG surge protectors are especially compact and available in multipolar versions to protect single or 3-phase AC networks, which makes them the best surge protection solution for Type 1 requirements.
Select another reference:
SPD type following IEC test |
1+2+3 |
Max. AC operating voltage L-N |
275 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnection |
335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection |
440 Vac withstand |
Residual Current Leakage current to Ground |
None |
Follow current |
None |
Nominal discharge current 15 x 8/20 µs impulses |
20 kA |
Max. discharge current max. withstand @ 8/20 µs by pole |
50 kA |
Impulse current by pole max. withstand 10/350µs by pole |
12.5 kA |
Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50µs - 8/20µs |
20 kV |
Withstand on overvoltages IEEE C62.41.1 |
20 kV |
Admissible short-circuit current |
50000 A |
Protection level @ In (8/20µs) |
1.5 kV |
Specific energy by pole max. withstand 10/350 µs |
40 kJ/ohm |
Technology | VG |
SPD configuration | 1-pole |
Connection to Network | by screw terminals: 2.5-25 mm² |
Format |
Plug-in modular box |
Mounting |
Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Failsafe behavior | Disconnection |
Disconnection indicator | 1 mechanical indicator |
Spare module(s) |
MDAC1-13VG-275 |
Remote signaling of disconnection |
option DAC1-13VGS-10-275: output on changeover contact |
Dimensions |
See diagram |
Certification |
- |
Standards compliance |
IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Installation ground fault breaker | Type 'S' or delayed |
Thermal disconnector | Internal |
Fuses |
Fuses Type gG - 125 A |